Hrvatski normativni dokument

Oznaka: HRN EN 1366-8:2024
Naslov (HR): Ispitivanja otpornosti servisnih instalacija na požar -- 8. dio: Kanali za odimljavanje (EN 1366-8:2024)
Naslov (EN): Fire resistance tests for service installations -- Part 8: Smoke extraction ducts (EN 1366-8:2024)
Područje primjene (EN): This document specifies a test method for determining the fire resistance of smoke extraction ducts. It is applicable only to smoke extraction ducts that pass through another fire compartment apart from the compartment from where smoke needs to be extracted in case of fire. It represents fire exposure of a fully developed fire.
This method of test is only applicable to fire resistant ventilation ducts (same construction) with the following classification according to EN 13501-3:
- fire from inside and outside i ↔ o;
- applicable to a pressure difference up to 500 Pa in fire conditions;
NOTE 1 It is assumed that the duct A test(s) in accordance with EN 1366-1 has been performed with an under-pressure of minimum 500 Pa.
- with integrity (E) and insulation (I) criteria equal to or higher than the intended classification for the smoke extraction duct.
For the purposes of the test described in this document, the duct is referred to as duct C.
This test method has been designed to cover both vertical and horizontal smoke extraction ducts. A vertical system need not be evaluated to this method provided that:
- both horizontal (ho) and vertical (ve) classification according to EN 13501-3 has been obtained for the ventilation duct;
- it has been tested in a horizontal orientation to this method.
If the ventilation duct in practise is only used for vertical applications in smoke extraction systems, only vertical (ve) classification is obtained in accordance with EN 13501-3 and tested only in a vertical orientation to this test method.
This test method is suitable for ducts constructed from non-combustible materials (class A1 and A2-s1, d0 according to EN 13501-1).
NOTE 2 Reaction with components of the duct can affect the oxygen concentration inside the duct leading to inaccurate calculation of the leakage rate. If it is determined this has happened refer to Annex D.
This document applies to four sided rectangular and circular ducts only (with fire exposure on all sides). Ducts that utilize elements of construction for one, two or three sides are not covered. An alternative test method for one, two and three sided ducts will be developed separately.
Izdanje: 2
ICS: 13.220.20 Zaštita od požara
13.220.50 Vatrootpornost građevnih materijala i elemenata
Tehnički odbor/pododbor: TO 92, Zaštita od požara
Oznaka faze: 60.60 - HRN dostupan
Glasilo (rasprava): HZN e-Glasilo 5/2023 ()
Glasilo (objava): HZN e-Glasilo 11/2024 ()
Način prihvaćanja: pr - prihvaćanje strane norme u izvorniku
Jezik: en
Broj stranica: 59
Cjenovni razred: K
Cijena: 52,00 EUR
Izvornik: EN 1366-8:2024
Zamjenjuje: HRN EN 1366-8:2007

Obrazac za naručivanje normativnih dokumenata i/ili publikacija (obrazac ob.025-2)   [preuzmite doc]   [preuzmite pdf]

Prijava korisnika

Mrežna stranica koristi kolačiće (cookies). Kolačiće upotrebljavamo kako bismo personalizirali sadržaj i oglase, omogućili značajke društvenih medija i analizirali promet. Isto tako, podatke o vašoj upotrebi naše web-lokacije dijelimo s partnerima za društvene medije, oglašavanje i analizu, a oni ih mogu kombinirati s drugim podacima koje ste im pružili ili koje su prikupili dok ste upotrebljavali njihove usluge. Nastavkom korištenja naših internetskih stranica vi prihvaćate našu upotrebu kolačića. Polica privatnosti.